24, 32 and 50kg/h (Zone 1 and Zone 2)

  • Gas inlet connection
  • Gas outlet connection
  • Gas probe
  • Safety relief valve
  • Water drain plug
Operation :
Model KTD 2001 Electric Dry Vaporizer

KTD 2001 electric vaporizers safely and efficiently vaporize LPG for commercial and industrial applications serving up to 50 kg/h. Eight (8) removable resistance heating elements inserted from the top extend through the vaporizer providing thermal energy to the aluminum heat exchanger placed inside an iron pressure vessel. The control housing containing electric components and mechanical thermostats is placed on the side allowing easy accessible maintenance. The control housing is equipped with a green on/off indicator light. The standard Remote Control Panel can be placed next to the vaporizer or in a designated control room depending on the classification of the room.

When the vaporizer reaches operating temperature, the inlet solenoid valve will open to allow gas flow. The inlet solenoid valve is controlled by a mechanical thermostat located in the vapor outlet. The vaporizer is equipped with a mechanical excess temperature protection thermostat to ensure that the vaporizer is not overloaded. Other mechanical thermostats monitor the temperature of the LPG and the aluminum heat exchanger, and regulate the on/off cycle of the heating elements at predetermined set points.

Standard Features :
Explosion proof classification
Zone 1 :
EEx d m II A T3,
EN 50014, EN 50018, EN 50028
Zone 2 classification meets :

IEC 79-15

  • Pressure vessel designed to ASME specifications
  • Eight (8) individually removable high quality heating elements
  • Reliable mechanical thermostats for operation and over temperature protection
  • Easily accessible control housing with green on/off indicator light
  • Inlet safety solenoid valve
  • Fully insulated
  • All metal surfaces are mechanically cleaned, primed and painted
External pressure relief valve : 25 bar (360 psi) or
17.6 bar (250 psi).

Approvals :
DEMKO (UL subsidiary) and PED (Pressure Equipment Directive) approvals with CE marking.
Scope of supply :
  • Installation and maintenance manuals
  • Pressure and electrical test certificates ( test pressure 38.5 bar (519 psig) )
Optional features :
  • Oil separator for drainage of residues
  • Regulators
  • Crating of vaporizer
  • Remote Control Panel indicating power on/off, solenoid valve on/off, heating elements on/off and overheating
Capacity kg/h
Gas Inlet /
Outlet
Norm
Connected
Load
KW
Phase
Voltage
V
50/60 Hz
Weight
Net
kg
Height
A
mm
Width B
mm

Dimension C
mm

Dimension
D
mm
24
BSP 1/2" BSP 1/2"
5.4
Single
230 - 600
70
875
230
440
145
32
BSP 1/2" BSP 1/2"
7.2
Three
400 - 600
70
875
230
440
145
50
BSP 1/2" BSP 1/2"
10.0
Three
400 - 600
70
875
230
440
145
 

Contact Us